Fan Coil Units 340 - 2380m3h - Condu Series

Chillers System

This ducted fan coil unit is designed for high efficiency, durability, and stable performance in commercial and residential HVAC applications. It uses a high-quality galvanized steel casing, precision-engineered copper tube & blue fin coil, and a forward-curved centrifugal fan to ensure strong air delivery with low noise operation. The unit is factory tested to guarantee cooling and heating performance and is suitable for concealed ceiling installations where compact size, reliability, and quiet operation are required. Optional components such as air filters, stainless-steel drain pans, extended drain pans, and plenum boxes allow flexible configuration to meet different project needs.

Casing

  • High-quality galvanized steel

  • 0.7 mm thickness for top & bottom plates

  • 1.0 mm thickness for coil end plate & motor deck

  • Ensures strong structure and long service life

Coil

  • Seamless copper tubes with blue aluminum fins

  • Expanded together for high heat transfer efficiency

  • Designed using professional coil selection software

  • Factory lab tested for guaranteed performance

  • Counter-flow design for higher efficiency

Coil Header

  • High-quality brass header

  • Low water pressure resistance design

  • Factory-built air vent valve

  • Protective mounting bracket to prevent damage during piping installation

Fan Blower

  • Forward-curved centrifugal fan

  • Each fan dynamically and statically balanced for low vibration and noise

Motor

  • Three-speed PSC motor

  • Easy capacitor maintenance

  • 100% incoming inspection and testing before use

Plenum (Optional)

  • 0.7 mm galvanized steel casing panels

  • Installed based on customer requirements

Supply & Return Air Flange

  • 0.7 mm galvanized steel flanges for all air connections

Filter (Optional)

  • Standard: 3 mm washable nylon filter

  • Optional: aluminum filter or sandwich-style filter

Drain Pan

  • Standard carbon-steel drain pan with anti-corrosion coating

  • One-time molding (no welding points)

  • Fully insulated with 5 mm PE insulation at bottom

  • Optional: stainless steel drain pan or extended drain pan

Download the catalog to view specifications for other models.

Condition Model
34 51 68 85 102 136 170 204 238
Nominal Air Flow H (m³/h) 360 530 700 870 1030 1420 1740 2100 2400
Nominal Air Flow M (m³/h) 285 420 560 660 820 1120 1380 1600 1850
Nominal Air Flow L (m³/h) 210 310 420 510 590 790 1000 1180 1450
Cooling Capacity H (kW) 1.95 2.83 3.77 4.55 5.5 7.25 8.59 10.4 11.6
Cooling Capacity M (kW) 1.7 2.5 3.3 4.0 4.9 6.5 7.5 9.3 10.3
Cooling Capacity L (kW) 1.4 2.0 2.7 3.3 4.0 5.4 6.1 7.5 8.4
Sensible Cooling H (kW) 1.4 2.0 2.7 3.2 3.9 5.4 6.2 7.4 8.2
Sensible Cooling M (kW) 1.2 1.8 2.4 2.9 3.5 4.8 5.5 6.6 7.3
Sensible Cooling L (kW) 1.0 1.4 2.0 2.3 2.8 3.9 4.4 5.3 5.9
Heating Capacity H (kW) 3.48 4.7 6.3 7.7 9.1 13.6 15.3 18 19
Heating Capacity M (kW) 2.9 3.9 4.8 6.4 7.6 10.6 12.1 14.6 16.6
Heating Capacity L (kW) 2.2 3.0 3.6 4.9 5.8 8.1 9.2 11.1 12.7
Water Flow (m³/h) 0.34 0.49 0.65 0.78 0.95 1.25 1.48 1.79 2.00
Noise Level 12Pa dB(A) 37 39 41 43 45 46 48 50 52
Noise Level 30Pa dB(A) 40 42 44 45 47 48 50 52 54
Noise Level 50Pa dB(A) 41 44 46 47 49 50 52 54 55
Power Supply: AC 1N 220V 50Hz
Power Input 12Pa (W) 37 51 62 76 96 140 154 194 228
Power Input 30Pa (W) 44 59 72 88 111 156 178 215 257
Power Input 50Pa (W) 48 65 84 99 122 174 208 250 300
Current 12Pa (A) 0.17 0.23 0.28 0.35 0.44 0.64 0.70 0.88 1.04
Current 30Pa (A) 0.20 0.27 0.33 0.40 0.50 0.71 0.81 0.98 1.17
Current 50Pa (A) 0.22 0.30 0.38 0.45 0.55 0.79 0.95 1.14 1.36
Water Resistance (kPa) 8 17 26 37 62 30 36 47 65
Drainage 3/4" MPT
Water Connection (Inlet) 3/4" FPT
Water Connection (Outlet) 3/4" FPT