Water to Water Standard & Heat Recovery – E Series (11.3 kW to 45.2 kW)

Chillers System

The Water to Water Standard & Heat Recovery E Series units are designed to supply chilled water and/or hot water to terminal units such as air handling units, fan coil units, and radiant floor heating systems. The units can also provide domestic hot water through heat recovery during cooling operation. The series is available in 9 sizes ranging from 11.3 kW to 45.2 kW and is offered in both single-circuit and dual-circuit configurations depending on the model size. Each unit is fully factory tested before shipment to ensure stable performance and reliability. The system uses environmentally friendly R410A refrigerant, high-efficiency rotary or scroll compressors, brazed-plate water-to-refrigerant heat exchangers, and microprocessor-based intelligent control. The robust galvanized steel cabinet with internal insulation minimizes noise and condensation, while multiple water connection options allow flexible system integration.

Functional & Application Features

  • Supplies chilled water, hot water, and domestic hot water (heat recovery)

  • Supports water loop and geothermal system applications

  • Cooling + heating + heat recovery operation modes

  • Factory run-tested before delivery

  • Capacity range: 11.3 kW – 45.2 kW

Environmental & Efficiency

  • Environment-friendly R410A refrigerant (zero ozone depletion)

  • High-efficiency rotary compressors

  • Brazed-plate stainless-steel heat exchangers with anti-corrosion design

Control & Protection

  • Microprocessor-based controller

  • Five operation modes (cooling, heating, heat recovery, domestic hot water, heating + domestic hot water)

  • LCD display with water temperature indication (load side, source side, domestic hot water)

  • RS485 BMS communication interface

  • High/low pressure protection, antifreeze protection, flow switch protection

  • Low-pressure switch bypass during compressor startup

Mechanical & Construction

  • G-60 galvanized steel cabinet

  • 15 mm thick insulated panels for noise reduction and anti-condensation

  • Independent electrical control box section

  • Threaded water connections for load side, source side and domestic hot water side

  • Optional integrated pumps for load water, source water and hot water circuits

Item Model MSR-J036 MSR-J052 MSR-J072 MSR-J086 MSR-J100 MSR-J120 MSR-J142
Cooling Capacity kW 11.3 14.5 17.6 22.1 29.1 33.1 43.5
Heating Capacity kW 15.5 19 23.7 30 38.1 43.8 58.8
Cooling Power kW 2.3 3.0 3.7 4.6 6.1 7.2 9.3
Heating Power kW 2.9 3.6 4.5 5.7 7.4 8.7 11.3
Power Supply   380V / 3N~ / 50Hz
Cooling Current A 5.8 6.1 7.3 9.2 11.9 13.3 18.7
Heating Current A 6.4 7.1 8.2 11.0 14.0 16.2 21.9
Compressor Type   High Efficiency Rotary
Compressor Qty   1 1 1 1 2 2 2
Refrigerant   R410A
Load Water Flow m³/h 1.9 2.5 3.0 3.8 5.0 5.7 7.5
Load Pressure Drop kPa 48 53 55 59 65 67 68
Source Water Flow m³/h 2.4 3.0 3.7 4.6 6.1 6.9 9.1
Source Pressure Drop kPa 52 55 58 59 68 69 69
Source Connection Fitting Size (Without Pump) in R 1-1/4
Load Connection Fitting Size (Without Pump) in R 1-1/4
Hot Water Capacity L/h 245 305 380 450 305 380 450
Hot Water Flow m³/h 2.2 2.7 3.4 4.1 2.7 3.4 4.1
Connection Fitting Size (Hot Water) in R 1
Hot Water Pump (Standard) Head (m) 5~8 5~8 5~8 5~8 10~15 10~15 10~15
Power (kW) 0.21 0.21 0.21 0.21 0.37 0.37 0.37
Connection Size R 1
Load Water Pump (Standard) Head (m) 26 24 27 24 28 30 27
Power (kW) 0.55 0.55 0.55 0.55 0.75 1.1 1.1
Connection Size Rp 1 Rp 1 1/4 Rp 1 1/2
Source Water Pump (Optional) Head (m) 29 27 25 27 28 27 25
Power (kW) 0.55 0.55 0.55 0.75 1.1 1.1 1.1
Connection Size Rp 1 1/4 Rp 1 1/2  
Weight (Net/Gross) kg 175/200 180/205 185/210 190/215 245/280 265/300 285/320
Dimensions (L × W × H) mm 675 × 580 × 1350 675 × 880 × 1350